The G3-U16 module has 16 optically isolated, current source digital outputs at 24 VDC± 25%, 2A max directly power loads in VDC within the limits of rated currents, or control loads of any kind via solid state relay, contactors.
G3-U16 can be connected with all the G-Mation gateways and Px modules from which it receives power supply.
The outputs are divided into 4 groups of 4 outputs, with maximum current of 6A per group.
Each output is protected against short-circuit, overload and overheating.
There is an Internal demagnetization circuit for inductive loads.